AI Insight

Smart recommendations

Heat Loss Calculator

Calculate how much heat your building loses — and how much heating power you need to stay warm.

Want to see savings from better insulation? Insulation Savings Calculator →

Project

Temperatures

Target room temperature
Coldest design day
Heating degree days

Design outdoor temperature is used for peak heat load (heating system sizing). HDD is used for annual energy demand. Typical HDD: Oslo ~4300, London ~2700, Paris ~2600, Munich ~3400.

Building Elements

Add each building element: walls, roof, floor, windows, doors. Enter its area and U-value.

Element
Area (m²)
U-value (W/m²K)
Used to estimate annual heating cost.
Heat pumps deliver more heat than the electricity they use.

Results

Peak heat load
watts (minimum boiler / heat pump size)

Peak load covers conduction only — add 10–20% for ventilation and infiltration. Annual energy assumes continuous heating during heating season.

Typical U-values for reference

Single glazing
5.7 W/m²K
Double glazing (old)
2.8 W/m²K
Double glazing (modern)
1.4 W/m²K
Triple glazing
0.8 W/m²K
Uninsulated solid wall
2.1 W/m²K
Uninsulated cavity wall
1.5 W/m²K
Well insulated wall
0.18 W/m²K
Uninsulated flat roof
2.3 W/m²K
Well insulated roof
0.13 W/m²K
Uninsulated ground floor
0.7 W/m²K
Well insulated floor
0.13 W/m²K
Solid timber door
3.0 W/m²K
See how much you save by improving insulation
Compare before/after U-values and get annual savings, 10-year saving and payback period.
Insulation Savings Calculator →

Common questions about heat loss & heating system sizing

What size boiler do I need for my house?+

Boiler size is determined by your home's peak heat loss in kilowatts. A typical 3-bedroom semi-detached house with cavity walls and double glazing loses around 5–8 kW on the coldest day. Add 20% for ventilation losses and domestic hot water, giving a recommended boiler size of 7–12 kW. Older uninsulated homes can need 12–20 kW.

What size heat pump do I need?+

Heat pumps are sized to peak heat loss, just like boilers — but they work best when slightly undersized and run continuously rather than cycling. A well-insulated 100 m² home typically needs a 5–8 kW heat pump. Older uninsulated homes may need 12–16 kW. Improving insulation before installing a heat pump significantly reduces the required size and running cost.

How do I calculate heat loss through a wall?+

Heat loss (W) = U-value × Area (m²) × ΔT (°C). Example: a 20 m² wall with U-value 1.5 W/m²K and ΔT of 31°C (inside 21°C, outside −10°C) loses 20 × 1.5 × 31 = 930 W. Add all building elements together for the total peak load.

How much does it cost to heat a house per year?+

A typical 100 m² home in central Europe with moderate insulation needs around 10,000–15,000 kWh/year for space heating. At €0.28/kWh with a gas boiler (90% efficiency): roughly €3,100–€4,700/year. The same home with a heat pump at COP 3.5 would cost €800–€1,200/year in electricity — a saving of €2,000–€3,500 annually.

What is a U-value?+

A U-value measures how much heat passes through a building element per m² per degree of temperature difference (W/m²K). Lower = better insulation. Single glazing: ~5.7. Double glazing: 1.4–2.8. Well-insulated wall: 0.18. Passivhaus wall: 0.10. The reference table on this page lists typical values for common construction types.

How to calculate building heat loss

The formula

Heat loss (W) = U-value × Area × ΔT

Where U-value is in W/m²K, area in m², and ΔT is the temperature difference between inside and outside in Kelvin (same as °C difference).

Add up the heat loss through every building element — walls, roof, floor, windows, doors — to get the total peak heat load.

Peak heat load vs. annual energy demand

Peak heat load (watts) tells you the minimum size of your boiler or heat pump — it must cover the worst-case winter day. Annual heat demand (kWh) tells you what you'll spend on heating over a year, which is where heating degree days come in.

What are heating degree days?

Heating degree days (HDD) count how many degrees below a base temperature (usually 15.5°C or 18°C) the average daily temperature falls. A year with HDD 3000 means the heating season is 3000 degree-days long. Annual energy demand = heat loss per degree × HDD × 24 hours.

What about ventilation losses?

This calculator covers conduction losses only. In a real building, ventilation and infiltration (draughts) add another 10–30% on top. For a full Manual J / EN 12831 calculation, use a specialist tool or consult a building services engineer.

Pro tip: Windows are often the weakest link — a 10 m² wall with U=0.2 loses the same heat as a 1.4 m² double-glazed window. Upgrading glazing can make a big difference in high heat-loss homes.
🏠 Hub